Hartford Tank Removal Research is the independent research and reference section of hartfordctoiltankremoval.com.
Heating Oil Tank Size Chart: Dimensions, Capacities and Inch-to-Gallon Data
Granby Industries' and Highland Tank's published charts for nominal 275-gallon vertical tanks differ by no more than 1.6 gallons at any of 44 matched one-inch depths; the nominal 330-gallon comparison reaches 6.5 gallons.
A heating oil tank size chart is only useful once you know which tank it applies to. This release assembles 55 manufacturer-documented model or configuration records from Granby Industries, Highland Tank and Roth North America and finds six distinct footprints carrying a nominal 275-gallon label. The mean absolute difference in the matched 275-gallon comparison is 0.6 gallon. These charts are not interchangeable. This page publishes the dimensions, matched row comparison, source cells, methods and exclusions that determine which chart applies.
What are the key heating oil tank size chart statistics?
These figures lead with the numbers most likely to be needed in a deadline-driven lookup. Each line is self-contained, names its source and carries the July 27, 2026 verification date.
1. Granby's and Highland Tank's published vertical charts for a nominal 275-gallon tank differ by no more than 1.6 gallons at any matched one-inch depth across all 44 rows; the mean absolute difference is 0.6 gallon. Calculated July 27, 2026 from Granby Industries, "Capacity Chart for Vertical Tanks," and Highland Tank, "Tank Gauge Charts" HT-6000-01/2021.
2. The same comparison for nominal 330-gallon vertical tanks reaches a peak absolute difference of 6.5 gallons with a mean of 3.4 gallons. Calculated July 27, 2026 from the same manufacturer charts.
3. This dataset documents six distinct manufacturer footprints carrying a nominal 275-gallon label: two Granby steel obround orientations, two Highland Tank orientations, the Roth EcoDWT plus 3 1000L and the Roth EcoDWT plus 3 1000LH. They do not share one conversion chart and they do not fit the same spaces. Granby Industries, Highland Tank and Roth North America manufacturer documents, verified July 27, 2026.
4. Granby's published vertical 275-gallon chart reaches 273.8 gallons at its final depth of 44 inches; Highland Tank's comparable chart reaches 275 gallons at 44 inches. Granby Industries and Highland Tank manufacturer charts, verified July 27, 2026.
5. In Granby's seven-column vertical chart, the 120- and 240-gallon columns continue to 47 inches and finish at 123 and 245 gallons, respectively; four other columns end at 44 inches below their nominal labels, and the 230-gallon column has no matching model in Granby's current U.S. Standard lineup. Granby Industries, "Capacity Chart for Vertical Tanks," verified July 27, 2026.
6. In Highland Tank's four-column vertical chart, the final 44-inch rows read 135, 226, 275 and 325 gallons against nominal labels of 137, 230, 275 and 330 — three of four series end below their labels. Highland Tank, "Tank Gauge Charts" HT-6000-01/2021, verified July 27, 2026.
7. Seven dealer, inspection and practitioner sources publish about 225 to 251 gallons for a "full," "usable," "maximum-fill" or delivered 275-gallon tank, but they are not measuring one consistently defined quantity. Definition-divergence audit completed July 27, 2026; no combined average is published.
8. Granby states that its capacity charts have about ±2% precision and are not intended for purchases or sales of products. Granby Industries, "Capacity Chart for Vertical Tanks," verified July 27, 2026.
9. Roth's EcoDWT plus 3 chart uses a 95% maximum-fill framework, states that filling above 95% is not permitted and says vent-whistle length may reduce the maximum further. Roth North America, fill chart and installation manual, verified July 27, 2026.
10. UL 80 covers aboveground atmospheric steel tanks from 60 to 660 U.S. gallons and permits cylindrical, rectangular or obround shapes in horizontal or vertical orientations. UL Standards & Engagement, UL 80 scope, verified July 27, 2026.
11. Granby's vertical 275-gallon chart adds 1.8 gallons in the first inch, reaches a maximum one-inch increment of 7.2 gallons in the straight middle section and adds 1.8 gallons from 43 to 44 inches. Computed from Granby's published cells, July 27, 2026.
12. Federal UST rules exclude a tank storing heating oil for consumptive use on the premises at any capacity; the separate 1,100-gallon farm-or-residential exclusion applies to motor fuel stored for noncommercial purposes. 40 CFR 280.12, verified July 27, 2026.
13. Connecticut DEEP does not regulate a residential underground heating-oil tank serving four residential units or fewer, while a tank serving five or more units is nonresidential and falls under RCSA 22a-449(d)-1; 2,100 gallons is a partial-exemption threshold inside that nonresidential program, not the point at which the program first applies. Connecticut DEEP, verified July 27, 2026.
14. The 2024 ACS estimates 509,593 ±10,057 occupied Connecticut housing units used "fuel oil, kerosene, etc." out of 1,455,235 ±6,160 occupied units — 35.0% — versus 4,654,835 ±35,907 of 132,737,146 ±140,273 nationally, or 3.5%. U.S. Census Bureau table B25040, 2024 one-year estimates, released September 11, 2025 and verified July 27, 2026.
15. The 2024 ACS estimates 5,216 ±1,356 occupied housing units in Hartford city used "fuel oil, kerosene, etc." out of 49,316 ±2,736 occupied units — 10.6%. U.S. Census Bureau table B25040, 2024 one-year estimates, verified July 27, 2026.
What does the heating oil tank size chart show by model?
Nominal capacity does not identify a tank. Across the 55 manufacturer-documented records, 22 distinct nominal capacities appear in different shapes and orientations, so manufacturer, construction, model and orientation must be matched before a conversion chart applies.
Dimensions are shown in the order the manufacturer publishes them. Where a source gives height, width and length, the table keeps that order rather than silently reordering the figures.
Steel obround tanks
"Obround" means a rectangle capped with semicircular ends — the flattened oval seen on the end of many basement tanks. UL 80 permits obround construction, and that changing cross-section is why gallons per inch is not a straight line.
Table 1. Steel obround heating-oil tank dimensions
| Manufacturer | Product no. | Nominal gal | Orientation | H | W | L | Gauge | Listing |
|---|---|---|---|---|---|---|---|---|
| Granby | 209101 | 120 | Vertical | 46″ | 23″ | 30″ | 12 | UL 80 |
| Granby | 208101 | 138 | Vertical | 44″ | 27″ | 30″ | 12 | UL 80 |
| Granby | 208601 | 138 | Horizontal | 27″ | 44″ | 30″ | 12 | UL 80 |
| Granby | 207101 (Stubbies) | 220 | Vertical | 44″ | 27″ | 48″ | 12 | UL 80 |
| Granby | 202201 (Narrow) | 240 | Vertical | 46″ | 23″ | 60″ | 12 | UL 80 |
| Granby | 202701 (Narrow) | 240 | Horizontal | 23″ | 46″ | 60″ | 12 | UL 80 |
| Granby | 204201 | 275 | Vertical | 44″ | 27″ | 60″ | 12 | UL 80 |
| Granby | 204701 | 275 | Horizontal | 27″ | 44″ | 60″ | 12 | UL 80 |
| Granby | 211201 | 275 | Vertical | 44″ | 27″ | 60″ | 10 | UL 80 |
| Granby | 211701 | 275 | Horizontal | 27″ | 44″ | 60″ | 10 | UL 80 |
| Granby | 204203 | 275 | Vertical | 44″ | 27″ | 60″ | 12 | UL 142 |
| Granby | 205201 | 330 | Vertical | 44″ | 27″ | 72″ | 12 | UL 80 |
| Granby | 205701 | 330 | Horizontal | 27″ | 44″ | 72″ | 12 | UL 80 |
| Granby | 205203 | 330 | Vertical | 44″ | 27″ | 72″ | 12 | UL 142 |
| Granby | 244201 (EcoGard) | 275 | Vertical | 44″ | 27″ | 60″ | 12 | UL 80 |
| Granby | 245201 (EcoGard) | 330 | Vertical | 44″ | 27″ | 72″ | 12 | UL 80 |
| Highland Tank | Basement 137 | 137 | Vertical | 44¼″ | 27″ | 30″ | — | not stated |
| Highland Tank | Basement 137 | 137 | Horizontal | 27″ | 44¼″ | 30″ | — | not stated |
| Highland Tank | Basement 230 | 230 | Vertical | 44¼″ | 22″ | 60″ | — | not stated |
| Highland Tank | Basement 275 | 275 | Vertical | 44¼″ | 27″ | 60″ | — | not stated |
| Highland Tank | Basement 275 | 275 | Horizontal | 27″ | 44¼″ | 60″ | — | not stated |
| Highland Tank | Basement 330 | 330 | Vertical | 44¼″ | 27″ | 72″ | — | not stated |
| Highland Tank | Basement 330 | 330 | Horizontal | 27″ | 44¼″ | 72″ | — | not stated |
Source: Granby Industries, Standard Residential Oil Storage Tank UL-80 product page and June 2026 residential-tank brochure; Highland Tank, Tank Gauge Charts HT-6000-01/2021. Retrieved July 27, 2026. Highland's chart book does not state a listing for these basement models.
Granby's listed vertical and horizontal 275-gallon configurations have the same 60-inch length, with height and width swapped. The vertical configuration is 44 inches high by 27 wide; the horizontal is 27 high by 44 wide. A dimension string that does not identify the order can therefore be misleading even when all three numbers are present.
Highland Tank lists 44¼ inches where Granby lists 44. The charts compared below therefore describe closely related nominal sizes, not dimensionally identical tanks; the comparison reports the published difference without assigning it to an undocumented cause.
Double-wall and nonmetallic tanks
These models carry manufacturer listings to UL SU 2258 or UL/ULC 2258 rather than UL 80. They also show why a nominal 275-gallon label does not predict shape or headroom.
Table 2. Double-wall and nonmetallic tank dimensions
| Manufacturer | Model | Nominal gal | H | W | L | Min. height required | Listing |
|---|---|---|---|---|---|---|---|
| Roth | EcoDWT plus 3 400L | 110 | 44″ | 28″ | 29″ | 49″ | UL SU 2258 |
| Roth | EcoDWT plus 3 620L | 165 | 61″ | 28″ | 29″ | 66″ | UL SU 2258 |
| Roth | EcoDWT plus 3 1000L | 275 | 61″ | 28″ | 43″ | 66″ | UL SU 2258 |
| Roth | EcoDWT plus 3 1000LH | 275 | 54″ | 30″ | 51″ | 60″ | UL SU 2258 |
| Roth | EcoDWT plus 3 1500L | 400 | 68″ | 30″ | 64″ | 76″ | UL SU 2258 |
| Granby | 961225 (2-in-1) | 190 | 48″ | 28″ | 44″ | — | UL/ULC 2258 |
| Granby | 961226 (2-in-1) | 265 | 64″ | 28″ | 44″ | — | UL/ULC 2258 |
Source: Roth North America, EcoDWT plus 3 Installation Instructions; Granby Industries, June 2026 residential-tank brochure and 2-in-1 product material. Retrieved July 27, 2026.
The minimum-height column is the one that catches people out. A Roth 1000L carries the same nominal 275-gallon label as a steel basement tank but requires 66 inches of installed height, while the low-profile 1000LH requires 60 inches.
Fiberglass tanks
Granby's two official brochures checked in this audit do not present an identical fiberglass lineup. The table uses the June 12, 2026 brochure for current values and labels rows that appear only in the official May 20, 2025 brochure.
Table 3. Granby fiberglass tank dimensions and source status
| Manufacturer | Model | Nominal gal | Orientation | H | W | L | Source status |
|---|---|---|---|---|---|---|---|
| Granby | 125N | 150 | Vertical | 44″ | 24″ | 52″ | Official 05/20/25 brochure; not listed in 06/12/26 brochure |
| Granby | 150N | 180 | Vertical | 47″ | 24″ | 60″ | 06/12/26 brochure |
| Granby | 175N | 210 | Vertical | 47″ | 24″ | 68″ | Official 05/20/25 brochure; not listed in 06/12/26 brochure |
| Granby | 200N | 240 | Vertical | 53″ | 24″ | 66″ | 06/12/26 brochure |
| Granby | 250N | 300 | Vertical | 53″ | 24″ | 80″ | 06/12/26 brochure |
| Granby | H150N | 180 | Horizontal | 28″ | 41″ | 59″ | 06/12/26 brochure |
| Granby | H175N | 210 | Horizontal | 28″ | 41″ | 68″ | Official 05/20/25 brochure; not listed in 06/12/26 brochure |
| Granby | H200N | 240 | Horizontal | 28″ | 48″ | 65″ | 06/12/26 brochure |
| Granby | D202 (double wall) | 240 | Vertical | 53″ | 24″ | 65″ | 06/12/26 brochure; older official brochure conflicts |
| Granby | D252 (double wall) | 300 | Vertical | 53″ | 24″ | 80″ | 06/12/26 brochure |
Source: Granby Industries official residential-tank brochures, revisions 06/12/26 and 05/20/25. Retrieved July 27, 2026. The D202 conflict is preserved in the source-integrity audit rather than reconciled silently.
Granby publishes separate capacity charts for some vertical fiberglass models. Those chart rows are outside the released 396-row chart CSV and are not reproduced on this page; a standard steel chart should not be substituted for a fiberglass model.
Highland Tank bench-top tanks
These four records are included so the visible tables account for all 55 model or configuration rows in the downloadable dimensions dataset. Highland's chart book supplies the dimensions but does not state a listing in the table used here.
Table 4. Highland Tank bench-top dimensions
| Manufacturer | Model | Nominal gal | Orientation / shape | H | W | L |
|---|---|---|---|---|---|---|
| Highland Tank | Bench Top 180 | 180 | Horizontal rectangular | 33″ | 22″ | 60″ |
| Highland Tank | Bench Top 280 | 280 | Horizontal rectangular | 36″ | 30″ | 60″ |
| Highland Tank | Bench Top 350 | 350 | Horizontal rectangular | 33″ | 42″ | 60″ |
| Highland Tank | Bench Top 500 | 500 | Horizontal rectangular | 33″ | 50″ | 72″ |
Source: Highland Tank, Tank Gauge Charts HT-6000-01/2021. Retrieved July 27, 2026.
Cylindrical and larger tanks
A nominal gallon number does not identify a cylindrical geometry either. The same nominal size can be assigned to different diameter-and-length combinations.
Table 5. Cylindrical and larger tank dimensions
| Manufacturer | Model | Nominal gal | Diameter | Length | Listing |
|---|---|---|---|---|---|
| Granby | 3005224 | 138 | 26″ | 60″ | UL 80 |
| Granby | 3011223 | 300 | 38″ | 60″ | UL 142 |
| Granby | 3020223 | 500 | 46″ | 72″ | UL 142 |
| Granby | 3020233 | 500 | 50″ | 60″ | UL 142 |
| Granby | 3039233 | 1,000 | 50″ | 120″ | UL 142 |
| Highland Tank | Horizontal 240 | 240 | 38″ | 4′0″ | not stated |
| Highland Tank | Horizontal 300 | 300 | 38″ | 5′0″ | not stated |
| Highland Tank | Horizontal 500 | 500 | 48″ | 5′5″ | not stated |
| Highland Tank | Horizontal 1,000 | 1,000 | 48″ | 10′9″ | not stated |
| Highland Tank | Horizontal 1,000 | 1,000 | 64″ | 6′0″ | not stated |
| Highland Tank | Horizontal 1,500 | 1,500 | 64″ | 9′0″ | not stated |
Source: Granby Industries, June 2026 residential-tank brochure; Highland Tank, Tank Gauge Charts HT-6000-01/2021. Retrieved July 27, 2026.
A nominal 500-gallon Granby cylinder appears in two geometries: 46 inches in diameter by 72 inches long and 50 inches in diameter by 60 inches long. Highland likewise publishes two 1,000-gallon horizontal geometries, so diameter alone does not identify the model.
Why does one 275-gallon label cover six footprints?
The label is a nominal product designation, not a complete model identifier. These six dimension sets are all supported by the manufacturer documents in this release.
Table 6. Six manufacturer-documented 275-gallon footprints
| Nominal | Manufacturer | Model | Footprint (H × W × L) | Cross-section |
|---|---|---|---|---|
| 275 gal | Granby | 204201 / 211201 / 204203 / 244201 | 44 × 27 × 60 in | obround |
| 275 gal | Granby | 204701 / 211701 | 27 × 44 × 60 in | obround |
| 275 gal | Highland Tank | Basement 275 vertical | 44¼ × 27 × 60 in | obround |
| 275 gal | Highland Tank | Basement 275 horizontal | 27 × 44¼ × 60 in | obround |
| 275 gal | Roth | EcoDWT plus 3 1000L | 61 × 28 × 43 in | rectangular |
| 275 gal | Roth | EcoDWT plus 3 1000LH | 54 × 30 × 51 in | rectangular |
Source: Granby Industries, Highland Tank and Roth North America manufacturer documents listed in the Sources section. Retrieved July 27, 2026.
Six footprints, one number. The tallest is 61 inches; the shortest is 27. The longest is 60 inches; the shortest is 43. They do not share one conversion chart and they do not fit the same spaces.
How do you tell what size heating oil tank you have?
The tank's data plate is the most direct identifier because it can supply the manufacturer, model or product number and nominal capacity. Where the plate is missing or illegible, exterior shape and all available dimensions can narrow the family, but they do not justify applying a chart whose model and orientation have not been matched.
What distinguishes tanks, in order of usefulness:
- The data plate. Record the manufacturer, model or product number and nominal capacity. Those fields are more specific than a generic "275-gallon" label.
- The end profile. A flattened oval taller than it is wide is a vertical obround; wider than tall is a horizontal obround. A flat-sided double-wall tank and a true cylinder require different reference data.
- All three exterior dimensions. A 60-inch length alone does not settle the model. Height, width and length together can distinguish a 44 × 27 × 60-inch vertical obround from a 27 × 44 × 60-inch horizontal one and from the Roth rectangular configurations.
- Documented delivery history as corroboration only. A past delivery can show that the tank held at least that much available volume at the time, but it does not establish the tank's nominal or maximum capacity.
Tank interiors, fill openings, vent lines and buried equipment are handled by qualified heating or tank professionals. Nothing on this page is a procedure for opening, probing, entering, cutting, disconnecting or otherwise working on a tank.
What do the published inch-to-gallon charts show?
A gallons-per-inch chart belongs to a specific tank shape, orientation and chart family. The tables below preserve manufacturer values, distinguish selected page rows from the released CSV's complete series and keep source conflicts visible rather than forcing unlike documents into one number.
Granby vertical tanks
Table 7. Granby vertical-tank gallons by liquid depth
| Depth | 120 gal | 138 gal | 220 gal | 230 gal | 240 gal | 275 gal | 330 gal |
|---|---|---|---|---|---|---|---|
| 1″ | 1 | 0.9 | 1.4 | 1.6 | 2 | 1.8 | 2.1 |
| 2″ | 2 | 2.5 | 4.0 | 4.6 | 5 | 5.0 | 6.0 |
| 4″ | 6 | 6.9 | 11.0 | 12.6 | 12 | 13.7 | 16.5 |
| 6″ | 11 | 12.6 | 20.1 | 22.4 | 22 | 25.1 | 30.2 |
| 8″ | 17 | 18.8 | 30.2 | 33.2 | 33 | 37.7 | 45.2 |
| 10″ | 23 | 25.6 | 41.0 | 44.7 | 45 | 51.2 | 61.4 |
| 12″ | 29 | 32.6 | 52.2 | 56.4 | 56 | 65.3 | 78.3 |
| 14″ | 34 | 39.8 | 63.7 | 68.2 | 68 | 79.6 | 95.5 |
| 16″ | 40 | 47.0 | 75.1 | 79.9 | 80 | 93.9 | 112.7 |
| 18″ | 46 | 54.1 | 86.6 | 91.6 | 92 | 108.2 | 129.9 |
| 20″ | 52 | 61.3 | 98.1 | 103.3 | 104 | 122.6 | 147.1 |
| 22″ | 58 | 68.5 | 109.5 | 115.0 | 116 | 136.9 | 164.3 |
| 24″ | 64 | 75.6 | 121.0 | 126.7 | 127 | 151.2 | 181.5 |
| 26″ | 70 | 82.8 | 132.5 | 138.4 | 139 | 165.6 | 198.7 |
| 28″ | 76 | 90.0 | 143.9 | 150.1 | 151 | 179.9 | 215.9 |
| 30″ | 82 | 97.1 | 155.4 | 161.8 | 163 | 194.3 | 233.1 |
| 32″ | 88 | 104.3 | 166.8 | 173.6 | 175 | 208.6 | 250.3 |
| 34″ | 94 | 111.3 | 178.1 | 185.3 | 187 | 222.6 | 267.2 |
| 36″ | 100 | 118.1 | 188.9 | 196.8 | 199 | 236.1 | 283.4 |
| 38″ | 106 | 124.3 | 198.9 | 207.6 | 210 | 248.7 | 298.4 |
| 40″ | 111 | 129.9 | 207.8 | 217.4 | 221 | 259.8 | 311.7 |
| 42″ | 116 | 134.4 | 215.0 | 225.4 | 231 | 268.7 | 322.5 |
| 44″ | 120 | 136.9 | 219.1 | 230.0 | 239 | 273.8 | 328.6 |
| 46″ | 123 | — | — | — | 243 | — | — |
| 47″ | 123 | — | — | — | 245 | — | — |
Source: Granby Industries, "Capacity Chart for Vertical Tanks," retrieved July 27, 2026. Granby states that precision is about ±2% and that the chart is not intended for purchases or sales of products. The page table shows selected rows; the released 396-row CSV contains complete one-inch Granby series for 138, 220, 230, 275 and 330 gallons, not the 120- or 240-gallon columns shown here directly from the source PDF.
The 230-gallon column has no matching model in Granby's current U.S. Standard product lineup. At the final published row, four of the seven columns finish below nominal — 138, 220, 275 and 330 — while the 120 and 240 columns continue beyond 44 inches to 123 and 245 gallons.
Highland Tank basement tanks
Table 8. Highland Tank vertical basement-tank gallons by liquid depth
| Depth | 137 gal V | 230 gal V | 275 gal V | 330 gal V |
|---|---|---|---|---|
| 2″ | 3 | 5 | 5 | 6 |
| 6″ | 12 | 22 | 25 | 30 |
| 10″ | 25 | 44 | 51 | 60 |
| 14″ | 39 | 67 | 79 | 93 |
| 18″ | 53 | 89 | 108 | 127 |
| 22″ | 67 | 112 | 136 | 161 |
| 26″ | 81 | 135 | 165 | 194 |
| 30″ | 95 | 158 | 193 | 228 |
| 34″ | 109 | 181 | 221 | 262 |
| 38″ | 122 | 203 | 248 | 292 |
| 42″ | 132 | 221 | 268 | 317 |
| 44″ | 135 | 226 | 275 | 325 |
Source: Highland Tank, "Tank Gauge Charts," HT-6000-01/2021, retrieved July 27, 2026. The page table shows selected even-numbered rows; the released CSV contains the complete 44-row vertical series for 137, 230, 275 and 330 gallons. Highland's separate horizontal tables are not included in the 396-row CSV.
Roth EcoDWT plus 3
Roth publishes gallons, liters and percentage full together for five models. The official installation manual and the standalone chart disagree at one 1000L cell, so the table uses the manual's internally consistent value and leaves the conflict visible.
Table 9. Selected Roth EcoDWT plus 3 fill-chart rows
| Depth | 400L (110 gal) | 620L (165 gal) | 1000L (275 gal) | 1000LH (275 gal) | 1500L (400 gal) |
|---|---|---|---|---|---|
| 10″ | 25 gal / 95 L / 22% | 25 gal / 95 L / 16% | 42 gal / 159 L / 16% | 48 gal / 180 L / 17% | 60 gal / 228 L / 14% |
| 20″ | 51 gal / 193 L / 44% | 51 gal / 193 L / 31% | 86 gal / 326 L / 31% | 100 gal / 380 L / 37% | 129 gal / 490 L / 30% |
| 30″ | 81 gal / 307 L / 70% | 81 gal / 307 L / 49% | 135 gal / 511 L / 49% † | 153 gal / 580 L / 56% | 196 gal / 740 L / 45% |
| 32″ | 89 gal / 337 L / 77% | 89 gal / 337 L / 54% | 148 gal / 56 L / 54% ⚠ | 164 gal / 620 L / 60% | 209 gal / 790 L / 48% |
| 39″ | 109 gal / 413 L / 95% ● | 109 gal / 413 L / 66% | 182 gal / 689 L / 66% | 200 gal / 760 L / 73% | 255 gal / 965 L / 73% |
| 49″ | — | 137 gal / 519 L / 83% | 228 gal / 863 L / 83% | 254 gal / 960 L / 95% ● | 323 gal / 1,223 L / 83% |
| 56″ | — | 157 gal / 594 L / 95% ● | 263 gal / 995 L / 95% ● | — | 375 gal / 1,420 L / 87% |
| 61″ | — | — | — | — | 412 gal / 1,560 L / 95% ● |
Source: Roth North America, EcoDWT plus 3 Installation Instructions and standalone Fill Chart, retrieved July 27, 2026. ● rows mark each model's published 95% row. † The installation manual prints 135 U.S. gallons at 30 inches; the standalone chart prints 125 while retaining 511 liters and 49%. ⚠ Both documents print 56 liters at 32 inches; 148 U.S. gallons converts to 560.3 liters. Roth states that filling above 95% is not permitted and that vent-whistle length may reduce maximum fill.
Why is no Granby horizontal steel chart published here?
Granby's U.S. Standard product page labels its capacity-chart link "Capacity Chart for US Horizontal Tanks," but the destination file is named and titled "Capacity Chart for Vertical Tanks." As verified July 27, 2026, that link therefore does not support a Granby horizontal gallons-per-inch table.
Highland Tank does publish separate horizontal tables. Its nominal 275-gallon chart reads 51 gallons at 10 inches in the vertical orientation and 97 gallons at 10 inches in the horizontal orientation, which shows why a vertical chart cannot be transferred to the rotated geometry. The Highland horizontal rows are not part of the released 396-row CSV and are not presented as Granby values.
How much do two manufacturers' charts for the same nominal vertical size disagree?
The released comparison aligns Granby and Highland Tank rows at each one-inch depth for nominal 230-, 275- and 330-gallon vertical tanks. The 275-gallon series stays within 1.6 gallons at every depth, while the 330-gallon series reaches 6.5 gallons; the reported means are mean absolute differences, not signed averages.
Table 10. Granby–Highland vertical-chart divergence
| Nominal size | Mean absolute difference | Largest absolute difference | Where it peaks | Granby at 44″ | Highland at 44″ |
|---|---|---|---|---|---|
| 275 gal vertical | 0.6 gal | 1.6 gal | 32″ (208.6 vs 207) | 273.8 | 275 |
| 230 gal vertical | 2.7 gal | 4.8 gal | 36″ (196.8 vs 192) | 230.0 | 226 |
| 330 gal vertical | 3.4 gal | 6.5 gal | 41″ (317.5 vs 311) | 328.6 | 325 |
Source: Hartford Tank Removal Research calculation from Granby Industries, "Capacity Chart for Vertical Tanks," and Highland Tank, "Tank Gauge Charts" HT-6000-01/2021. All 132 matched rows are in the downloadable divergence CSV; calculated July 27, 2026.
Granby lists the compared 275- and 330-gallon vertical tanks at 44 inches high; Highland lists 44¼ inches. The dataset therefore measures differences between closely related nominal sizes, not one physically identical tank, and it does not assign the observed spread to undocumented manufacturing or rounding choices.
Table 11. Final published chart row compared with nominal label
| Manufacturer | Nominal | Final published depth | Chart value at final row | Difference from label |
|---|---|---|---|---|
| Granby | 120 | 47″ | 123.0 | +3.0 |
| Granby | 138 | 44″ | 136.9 | −1.1 |
| Granby | 220 | 44″ | 219.1 | −0.9 |
| Granby | 230 | 44″ | 230.0 | 0.0 |
| Granby | 240 | 47″ | 245.0 | +5.0 |
| Granby | 275 | 44″ | 273.8 | −1.2 |
| Granby | 330 | 44″ | 328.6 | −1.4 |
| Highland Tank | 137 | 44″ | 135 | −2 |
| Highland Tank | 230 | 44″ | 226 | −4 |
| Highland Tank | 275 | 44″ | 275 | 0 |
| Highland Tank | 330 | 44″ | 325 | −5 |
Source: Granby Industries and Highland Tank manufacturer charts, retrieved July 27, 2026. "Difference from label" is chart value minus nominal label; the table does not treat the nominal label as a field measurement.
The comparison establishes that nominal labels and final chart rows are not interchangeable fields. It does not establish that either manufacturer's chart is wrong.
How much oil does a 275-gallon tank really hold?
The question mixes at least three quantities: nominal model capacity, liquid volume at a charted depth and an operational fill or usable amount. Granby and Highland publish 273.8 and 275 gallons at the final row of their compared vertical charts, while seven secondary sources publish about 225 to 251 gallons under definitions that are not consistent enough to combine.
Table 12. Published 275-gallon figures and what each source says it describes
| Source | Figure published | What the source describes | Checked |
|---|---|---|---|
| Granby Industries | 273.8 gal at 44″ | Charted liquid volume at final depth | 2026-07-27 |
| Highland Tank | 275 gal at 44″ | Charted liquid volume at final depth | 2026-07-27 |
| InspectAPedia | Tank label cited as "Maximum Fill 247" | A photographed manufacturer maximum-fill marking | 2026-07-27 |
| OilTankCharts | About 240 usable; 230–250 typical delivery | Usable and delivered-fill explanation | 2026-07-27 |
| Bottini Fuel | "Closer to 240" | Amount described as in the tank when full | 2026-07-27 |
| C&K Smith Superior | 225–250 usable | Usable oil | 2026-07-27 |
| Hocon Gas | "Closer to 225" | Amount described as actual capacity | 2026-07-27 |
| Burt's Reliable | "Only 225 or so" | Amount described as contents when full | 2026-07-27 |
| HeatingHelp practitioner thread | 226–251 reported deliveries; 235 cited as usable | Field reports and practitioner discussion | 2026-07-27 |
Source: each publication named in the table; URLs are listed in the Sources section. The seven nonmanufacturer sources are presented as a terminology audit, not as primary technical authority and not as inputs to an average.
Roth's 95% framework is manufacturer-specific evidence. Roth states that its EcoDWT plus 3 tanks are limited to 95% on its chart and that vent-whistle length can reduce the maximum further. That statement supports Roth's models; this page does not turn it into a universal percentage for every steel tank.
Vent-whistle position and installation details affect delivered volume. Roth expressly identifies whistle length as one reason the attainable maximum may be lower than the chart's 95% row. The reviewed secondary sources also use "usable," "full," "maximum fill" and "delivery" as if they were synonyms even when they are not.
A cited number must carry its definition. For manufacturer chart volume, use the model-specific row. For an operational fill amount, identify whose equipment and whose definition the number describes.
How was this collected and checked?
The release is a documentary dataset built from manufacturer and government sources checked July 27, 2026. It preserves source cells, publishes known conflicts and separates manufacturer measurements from calculations so every consequential number can be traced or reproduced.
Source hierarchy. Product dimensions, model capacities, listings and fill values were accepted from manufacturer product pages, brochures, installation manuals and capacity-chart PDFs. Federal and Connecticut claims were checked against the responsible regulator, current statute or regulation material. Dealer pages and the practitioner thread appear only in the explicitly labeled definition-divergence table.
What we collected. The release contains 55 model or configuration records across Granby Industries, Highland Tank and Roth North America; 22 distinct nominal capacities from 110 to 1,500 gallons; 396 complete one-inch chart rows across nine vertical series; 132 matched Granby–Highland comparison rows; and ten source-integrity findings. The nine complete series in the chart CSV are Granby 138, 220, 230, 275 and 330 gallons and Highland 137, 230, 275 and 330 gallons. Selected Granby 120/240, Roth and Highland-horizontal values shown on the page come directly from their primary documents but are not represented as part of that 396-row CSV.
Raw and normalized fields. A source's printed value stays visible. Where Roth documents conflict or a printed gallon/liter pair is internally inconsistent, the raw cells remain in the audit and any conversion is stored or stated separately; a calculated value never silently replaces a manufacturer cell.
Unit conversion. One U.S. liquid gallon equals 3.785411784 liters. A value obtained with that factor is labeled as a calculation, not a manufacturer measurement.
Chart comparison. For each matched depth, the signed field is Granby minus Highland and the absolute field is the magnitude of that difference. The summary means are arithmetic means of the 44 absolute differences for each nominal size.
Geometric consistency check. For a vertical obround shell, radius is half the width and the straight middle height is total height minus width. The circular-segment area at a depth below the lower radius was calculated as r² arccos((r − d) / r) − (r − d)√(2rd − d²); the middle adds a rectangle, and the upper curve uses the complementary segment. Cross-sectional area was multiplied by tank length and divided by 231 cubic inches per U.S. gallon.
Table 13. Reproducible obround-shell consistency check
| Published series | Fitted shell multiplier | Mean absolute error | Maximum absolute error |
|---|---|---|---|
| Granby 275 vertical, 44 × 27 × 60 | 1.021935 | 0.048 gal | 0.378 gal |
| Granby 330 vertical, 44 × 27 × 72 | 1.021985 | 0.041 gal | 0.454 gal |
| Highland 275 vertical, 44¼ × 27 × 60 | 1.016786 | 0.272 gal | 1.011 gal |
| Highland 330 vertical, 44¼ × 27 × 72 | 1.000486 | 0.329 gal | 1.485 gal |
Source: Hartford Tank Removal Research calculation from manufacturer dimensions and the 44-row vertical-chart series. Calculated July 27, 2026. The bare 27 × 44 × 60-inch Granby shell model, before the fitted multiplier, computes to 267.936 U.S. gallons at full depth.
The close Granby fit demonstrates that a simple obround-shell model is mathematically consistent with the published rows after one fitted multiplier. It does not disclose or prove Granby's internal engineering method.
This is a documentary dataset, not a field survey. The release reads manufacturer documents and official records; it does not measure installed tanks.
What did the source-integrity audit find?
The audit flags cross-document conflicts, internally inconsistent unit cells, label-versus-chart gaps and unavailable source links so they are visible rather than silently resolved. Publication treatment is stated for each finding.
Table 14. Source-integrity findings and publication treatment
| ID | Document | Finding | Publication treatment |
|---|---|---|---|
| SA-01 | Granby Industries, Standard Residential Oil Storage Tank UL-80 product page and linked capacity PDF | The product page labels its capacity-chart link "Capacity Chart for US Horizontal Tanks," but the linked file is named and titled "Capacity Chart for Vertical Tanks." | Publish the verified horizontal dimensions; do not publish or infer Granby horizontal gallons-per-inch values from that link. |
| SA-02 | Granby Industries, Capacity Chart for Vertical Tanks and current U.S. Standard product page | The chart contains a 230-US-gallon column, while the current U.S. Standard lineup lists 120, 138, 220, 240, 275 and 330 US gallons. | Keep the 230-gallon values as a chart-only column; do not assign current Granby catalog dimensions to it. |
| SA-03 | Granby Industries, Capacity Chart for Vertical Tanks | Granby states that precision is about ±2% and that the chart is not intended for purchases or sales of any products. | Carry the limitation with every Granby fill-chart table and in the page limitations. |
| SA-04 | Roth North America, Standalone EcoDWT plus 3 Fill Chart and Installation Instructions | At 30 inches for the 1000L model, the standalone chart prints 125 US gal / 511 L / 49%, while the official installation manual prints 135 US gal / 511 L / 49%. | Use 135 US gallons in the main table because it agrees with the manual, liters and percentage; preserve the standalone 125-gallon cell as a visible cross-document conflict. |
| SA-05 | Roth North America, Standalone EcoDWT plus 3 Fill Chart and Installation Instructions | At 32 inches for the 1000L model, both documents print 148 US gal / 56 L / 54%; 148 US gallons converts to 560.3 liters. | Preserve the printed 56-liter cell, store 560.3 liters as a separate calculation, and flag the row. |
| SA-06 | Roth North America, EcoDWT plus 3 product specifications and fill chart | The metric model names and the rounded U.S.-gallon nominal labels are not direct unit equivalents; for example, 1,000 liters equals 264.2 U.S. gallons while DWT 1000L is labeled 275 U.S. gallons. | Treat the model name and nominal U.S.-gallon figure as manufacturer designations; do not use one to recalculate the other. |
| SA-07 | Roth North America, EcoDWT plus 3 Fill Chart | The DWT 1500L is labeled 400 U.S. gallons, while its final published 95% row is 412 U.S. gallons at 61 inches. | Publish both figures with their definitions; do not label the difference a manufacturer error without further primary evidence. |
| SA-08 | Highland Tank, Tank Gauge Charts HT-6000-01/2021 | The final published vertical-chart rows differ from nominal labels for three of four series: 137→135, 230→226 and 330→325; the 275 series ends at 275. | Publish the chart values as printed and compare them without assigning an undocumented cause. |
| SA-09 | Seven dealer, inspection and practitioner sources | The reviewed secondary sources publish about 225 to 251 gallons while using different terms, including "maximum fill," "usable," "full" and delivery amounts. | Publish the range only as a definition-divergence audit; do not average it or present it as a single manufacturer measurement. |
| SA-10 | Granby Industries, Official residential-tank brochures, revisions 06/12/26 and 05/20/25 | The 06/12/26 brochure lists fiberglass D202 at 240 U.S. gallons and 53 × 24 × 65 inches; the official 05/20/25 brochure lists D202 at 300 U.S. gallons and 53 × 24 × 66 inches. | Use the 06/12/26 value in the current dataset and keep the older official value visible in the audit instead of silently reconciling it. |
Source: the Granby Industries, Roth North America and Highland Tank primary documents identified in each row; verified July 27, 2026. The same ten records, with source URLs, are in the downloadable source-integrity CSV.
Which tank-capacity thresholds change a standard or regulatory scope?
Capacity can change which technical standard or regulatory program applies, but similar-looking gallon thresholds govern different questions. The table separates manufacturer-listing scope, federal SPCC applicability, federal UST exclusions and Connecticut's residential/nonresidential rules instead of combining them into one ladder.
Table 15. Verified capacity thresholds and legal scope
| Capacity or condition | What the verified source says changes | Primary authority |
|---|---|---|
| 60–660 U.S. gal | Scope of UL 80 for aboveground atmospheric steel tanks for oil-burner fuels and other combustible liquids; the published scope permits cylindrical, rectangular and obround shapes in horizontal or vertical orientations. | UL 80 §§1.1–1.2 |
| 60–660 U.S. gal | Scope of UL 2258 for aboveground nonmetallic or composite primary tanks, secondary tanks and secondary containments. | UL 2258 §§1.1–1.2 |
| More than 1,320 gal aggregate aboveground, or more than 42,000 gal completely buried | One of three federal SPCC applicability criteria; the facility must also be non-transportation-related and reasonably capable of discharging to navigable waters or adjoining shorelines. | U.S. EPA, SPCC applicability |
| 1,100 gal or less | Federal UST-definition exclusion for a farm or residential tank storing motor fuel for noncommercial purposes. | 40 CFR 280.12 |
| Any capacity | Federal UST-definition exclusion for a tank storing heating oil for consumptive use on the premises where stored. | 40 CFR 280.12 |
| Four residential units or fewer | Connecticut's residential underground heating-oil category. DEEP does not regulate installation and use of these tanks under its UST program, while contamination and cleanup remain regulated. | Connecticut DEEP residential guidance |
| Five residential units or more | The heating-oil UST is nonresidential and is regulated under RCSA 22a-449(d)-1 when it is not also fueling an emergency generator. | Connecticut DEEP five-or-more-unit guidance |
| Less than 2,100 gal in specified nonresidential on-site-heating systems | A partial exemption can apply to qualifying double-wall systems installed on or after October 1, 2003 for notification and life-expectancy provisions; no UST is exempt from closure or failure requirements. | Connecticut DEEP 2026 UST regulations briefing |
Source: UL Standards & Engagement; 40 CFR 280.12; U.S. EPA SPCC guidance updated April 24, 2026; Connecticut DEEP residential guidance, five-or-more-unit guidance and May 6, 2026 UST regulations briefing. All checked July 27, 2026.
The federal heating-oil exclusion and the Connecticut program answer different questions. A tank excluded from the federal UST definition can still fall within a state program, and a Connecticut partial exemption below 2,100 gallons does not remove closure or failure requirements.
How do Connecticut rules change by tank type and capacity?
Connecticut draws the first residential line by the number of units served, not by a residential tank's gallon label. DEEP does not regulate the installation and use of a heating-oil UST serving four units or fewer under its UST program, while removal contractor, training, local-permit and leak rules still apply; a tank serving five or more units is nonresidential.
Residential systems serving four units or fewer.
Connecticut DEEP states that it does not regulate the installation and use of residential heating-oil tanks in this category under its UST program. DEEP also states that contamination from those systems and the cleanup of that contamination are regulated.
Permits and contractor roles.
DEEP directs owners to the local fire marshal and building department for permit requirements. Its residential guidance identifies home-improvement-contractor registration for tank work and a properly licensed plumber for oil piping. Former CGS §29-320 should not be cited as current authority: the General Assembly's current Chapter 541 states that the section was repealed effective July 1, 2017.
Training and insurance.
Current CGS §20-420 requires a contractor seeking the relevant residential underground-heating-oil-tank registration to demonstrate DEEP-approved hazardous-material training and at least $1 million in liability insurance. DEEP's current training page identifies 40-hour HAZWOPER training with annual eight-hour refreshers and the ICC U2 tank-decommissioning examination or an approved equivalent.
Removal deadline.
DEEP's residential FAQ answers "No" when asked whether a residential heating-oil UST must be removed by a specific deadline. The same answer states that a leaking tank must be promptly emptied and removed.
Known or discovered leaks.
DEEP states that a tank known to be leaking before removal must be removed by a permitted spill-cleanup contractor, and that a permitted spill-cleanup contractor must perform necessary remedial actions when a leak is discovered during removal.
Systems serving five or more residential units.
These are nonresidential heating-oil USTs under RCSA 22a-449(d)-1 unless the system also fuels an emergency generator, which changes the regulatory category. Connecticut's May 6, 2026 briefing makes clear that less than 2,100 gallons is a partial-exemption threshold for specified systems — not a blanket exemption from the program and not an exemption from closure or failure requirements.
Source: Connecticut DEEP, "Residential Home Heating Oil Tanks," "Residential Home Heating Oil Tanks—FAQs," "Underground Storage Tanks Serving Five or More Residential Units," "Residential Underground Home Heating Oil Tank Releases" and the May 6, 2026 UST regulations briefing; Connecticut General Statutes Chapters 400 and 541. Checked July 27, 2026.
See also: Oil Tank Removal Requirements by State (2026) — the full 50-state reference dataset including Connecticut and Hartford details.
What do current Census and consumption data show about heating oil?
Heating oil remains far more prevalent in Connecticut than in the country as a whole, while Hartford city is below the statewide share. The table uses the Census Bureau's own 2024 one-year estimates and margins of error and labels EIA's winter-consumption figure as a forecast rather than a measurement of every household.
Table 16. Current heating-oil and housing context
| Measure | Estimate | Margin of error | Reference period | Primary source |
|---|---|---|---|---|
| U.S. occupied units using "fuel oil, kerosene, etc." | 4,654,835 of 132,737,146, or 3.5% | ±35,907 numerator; ±140,273 total | 2024 | ACS B25040, 1-year |
| Connecticut occupied units using "fuel oil, kerosene, etc." | 509,593 of 1,455,235, or 35.0% | ±10,057 numerator; ±6,160 total | 2024 | ACS B25040, 1-year |
| Connecticut rank by state share | 4th among the 50 states | Calculated from state estimates | 2024 | ACS B25040, 1-year |
| Hartford city occupied units using "fuel oil, kerosene, etc." | 5,216 of 49,316, or 10.6% | ±1,356 numerator; ±2,736 total | 2024 | ACS B25040, 1-year |
| Connecticut median year housing built | 1967 | ±1 year | 2024 | ACS B25035, 1-year |
| Hartford city median year housing built | 1944 | ±4 years | 2024 | ACS B25035, 1-year |
| Average oil consumption per oil-heated U.S. household | About 400 gal | Forecast, not a survey margin | Winter 2025–26 | EIA Winter Fuels Outlook |
Source: U.S. Census Bureau American Community Survey tables B25040 and B25035, 2024 one-year estimates, released September 11, 2025; U.S. Energy Information Administration, Winter Fuels Outlook for 2025–26. Percentages and Connecticut's rank were calculated from the official estimates; verified July 27, 2026.
The ACS category is "fuel oil, kerosene, etc." and its universe is occupied housing units. The estimates do not count tanks, identify tank sizes or show whether a property's tank is aboveground or underground. EIA's roughly 400-gallon figure is an average winter forecast for oil-heated households, not evidence that one tank size became standard for a particular reason.
Which heating-oil tank safety facts belong with a size chart?
The relevant safety facts explain why model identity, weight, pressure rating and leak status cannot be treated as chart trivia. They do not provide a procedure for moving, opening, entering, cutting, disconnecting, testing or removing a tank.
Empty-tank weight is already substantial. Granby lists its 12-gauge 275-gallon standard tank at 250 pounds and its 10-gauge 275-gallon configuration at 330 pounds before fuel is added.
The standard tanks are not pressure vessels. Granby identifies a 5 PSIG factory pressure test and atmospheric-pressure operation for the U.S. Standard line. A test pressure is not permission to pressurize installed equipment.
Orientation and support are model-specific. A tank's listed orientation, legs, base and installation requirements come from the manufacturer's documentation. A chart does not determine whether an installed tank is structurally sound.
Leaks change the contractor and cleanup requirements. Connecticut DEEP directs known leaking residential underground tanks and necessary remediation to permitted spill-cleanup contractors. DEEP also states that a petroleum release to soil or water is a discharge to the waters of the state and that the responsible party must clean up the release.
Source: Granby Industries U.S. Standard product specifications; Connecticut DEEP residential release guidance. Checked July 27, 2026.
What are the limitations of this heating oil tank size chart?
Product lines and source files change. The current Granby brochure is revision 06/12/26, Highland's chart book carries HT-6000-01/2021 and Roth's reviewed chart/manual files predate this verification pass. A future revision can change a model, cell or source URL.
Charts require the right model and orientation. A nominal capacity alone does not establish the applicable cross-section or conversion table.
Charts assume the installation conditions represented by the publisher. A tank that is out of level, deformed, differently constructed or not positively identified can produce a different reading.
Low-depth precision is not separately specified. Granby states approximately ±2% precision but does not publish a separate low-depth error model in the chart, so this page does not turn that statement into a fixed-gallon allowance.
Granby excludes purchase-and-sale use. Granby says its capacity chart is not intended for purchases or sales of products. Neither the manufacturer charts nor this page are custody-transfer measurements.
Roth's 95% rule is a Roth-source statement. Roth says its EcoDWT plus 3 tanks must not be filled above the chart's 95% level and that vent-whistle length can lower the attainable maximum. This page does not apply that percentage automatically to every manufacturer's tank.
Nominal capacity is a product designation. Final chart rows can finish above, below or at the nominal number, and the label should not be substituted for a measured source cell.
No Granby horizontal values were inferred. The current U.S. Standard page's chart link resolves to a vertical chart, so the release publishes Granby horizontal dimensions without manufacturing a Granby horizontal fill table.
Fiberglass and 2-in-1 manufacturer charts exist but are outside the 396-row release. The chart CSV is limited to nine complete vertical series from Granby and Highland. Selected Roth rows and Granby 120/240 values appear on the page from primary documents but are not described as part of that CSV.
Granby's fiberglass D202 documents conflict. The current June 2026 brochure value is used in the model CSV, and the older official May 2025 value remains visible in the audit.
The 225-to-251-gallon secondary range is not one measurement. The sources use "full," "usable," "maximum fill" and delivery amounts differently; the page does not collapse them into an average.
ACS values are survey estimates. Counts and percentages carry the published margins of error, and the ACS fuel category combines fuel oil with kerosene and related fuels.
Law and agency guidance can change. The legal section records the sources and date checked; it is not a substitute for the authority governing a particular property on a later date.
This is not a tank inspection, environmental determination or settlement measurement. It does not replace the tank's data plate, manufacturer documentation, a qualified professional or the authority having jurisdiction.
Which figures and source gaps were excluded from publication?
The audit closes unresolved gaps by excluding the unsupported figure rather than leaving a placeholder or supplying an estimate. These exclusions are part of the release record and explain why several commonly repeated numbers do not appear in the final tables.
Granby horizontal gallons-per-inch values. The current U.S. Standard page's link points to a vertical chart. No value from that file is presented as a Granby horizontal value.
Current Granby dimensions for the chart-only 230-gallon column. The chart column remains published as a source cell, but it is not assigned a current U.S. Standard model or dimensions.
A Hartford County 2024 one-year figure. Hartford County's pre-2022 county geography is not used for a current county claim. The page publishes the supported Hartford city estimate and no Hartford County number.
Unverified model-code thresholds. Numeric IRC, IFC or NFPA 31 thresholds from third-party code pages were removed because the authoritative adopted text for the applicable jurisdiction was not directly verified in this pass.
The older Connecticut "45%" statement and an unverified 2014 comparison. They were removed rather than forced into the current ACS series, which uses a specific 2024 category and margins of error.
Unverified buried-tank dimension pairs. The draft's circulated dimension pairs were removed because no current primary manufacturer document supporting the configurations was verified.
A causal explanation for why 275 gallons became common. The EIA forecast and manufacturer dimensions do not establish that historical claim, so the page reports the measured context without assigning a cause.
What is included in the dataset download?
The release consists of four versioned CSV files that separate model dimensions, manufacturer chart cells, calculated chart differences and source-integrity findings. The files publish their source URLs and verification fields so the page's main claims can be checked without extracting them from prose.
Manufacturer, model, nominal U.S. gallons, cross-section, orientation, dimensions, listing, source document, source URL, source status, source note, verification tier and retrieval date.
Nine complete vertical manufacturer series with depth, published U.S. gallons, source, note and verification fields.
Matched nominal size and depth, both source values, signed difference, absolute difference, difference definition, source URLs and calculation date.
Organization, document, finding, publication treatment, source URL and verification date.
Dataset name: 2026 Heating Oil Tank Size and Fill-Level Crosswalk
Version: 2026-07-27.2
Publisher: Hartford Tank Removal Research
Coverage: United States manufacturer data with federal and Connecticut reference context
Last verified: July 27, 2026
What are the citation details for this page and dataset?
The details below identify the publication, page, dataset version and verification date. They are provided as neutral attribution metadata and do not request or condition any link, citation or reuse.
Publication: Hartford Tank Removal Research
Page title: Heating Oil Tank Size Chart: Dimensions, Capacities and Inch-to-Gallon Data
URL: https://hartfordctoiltankremoval.com/research/heating-oil-tank-size-chart/
Dataset: 2026 Heating Oil Tank Size and Fill-Level Crosswalk, version 2026-07-27.2
Last updated and verified: July 27, 2026
Bibliographic form: Hartford Tank Removal Research. "Heating Oil Tank Size Chart: Dimensions, Capacities and Inch-to-Gallon Data." 2026 Heating Oil Tank Size and Fill-Level Crosswalk, version 2026-07-27.2. July 27, 2026.
Manufacturer specifications and published chart values remain attributed to their publishers throughout. The cross-manufacturer data schema, 132-row divergence analysis, geometric consistency check and ten-record source audit are the work of Hartford Tank Removal Research.
What are the most frequently asked heating-oil tank chart questions?
These answers restate the page's primary lookup findings in forms that remain accurate when read by themselves. Each answer uses the same model, orientation and definition boundaries as the tables above.
What is the standard size of a home heating oil tank?
What are the dimensions of a 275-gallon oil tank?
How many gallons are in a 275-gallon tank at 22 inches?
How many gallons does a 275-gallon tank actually hold?
How many gallons is one inch of oil in a 275-gallon tank?
Are vertical and horizontal oil-tank charts the same?
Can dimensions alone identify a heating-oil tank?
Why does a chart list fewer or more gallons than the tank name?
What is the difference between a Roth 1000L and 1000LH?
Why is a Roth 1000L labeled 275 gallons?
Does Connecticut DEEP regulate residential underground heating-oil tanks?
Can this chart verify a heating-oil delivery I paid for?
Which primary sources support this page?
The manufacturer, regulator, statute and official statistical sources below support the technical and legal claims in the page. The final seven entries are secondary publications used only for the labeled 275-gallon terminology audit, not as substitutes for manufacturer specifications. All sources were retrieved or rechecked July 27, 2026 unless a document date is stated in its title.
- Granby Industries. Standard Residential Oil Storage Tank UL-80 product page. granbyindustries.com
- Granby Industries. Capacity Chart for Vertical Tanks. PDF
- Granby Industries. Residential and Light Commercial Tanks brochure, revision 06/12/26. PDF
- Granby Industries. Residential tank brochure, revision 05/20/25. PDF
- Granby Industries. 2-in-1 Double-Wall Oil Tank product page. granbyindustries.com
- Granby Industries. 2-in-1 720 L / 190-gallon capacity chart. PDF
- Granby Industries. 2-in-1 1,000 L / 265-gallon capacity chart. PDF
- Granby Industries. Fiberglass vertical single-wall oil-tank product page. granbyindustries.com
- Granby Industries. Fiberglass 200-imperial-gallon capacity chart. PDF
- Granby Industries. Fiberglass 250-imperial-gallon capacity chart. PDF
- Roth North America. EcoDWT plus 3 Fill Chart. PDF
- Roth North America. EcoDWT plus 3 Installation Instructions. PDF
- Highland Tank. Tank Gauge Charts HT-6000-01/2021. PDF
- UL Standards & Engagement. UL 80 published scope. shopulstandards.com
- UL Standards & Engagement. UL 2258 published scope. shopulstandards.com
- Electronic Code of Federal Regulations. 40 CFR 280.12—Definitions. ecfr.gov
- U.S. Environmental Protection Agency. Who is regulated by the SPCC Rule?. epa.gov
- Connecticut DEEP. Residential Home Heating Oil Tanks. portal.ct.gov
- Connecticut DEEP. Residential Home Heating Oil Tanks—FAQs. portal.ct.gov
- Connecticut DEEP. Underground Storage Tanks Serving Five or More Residential Units. portal.ct.gov
- Connecticut DEEP. Residential Underground Home Heating Oil Tank Releases. portal.ct.gov
- Connecticut DEEP. UST Clean-Up. portal.ct.gov
- Connecticut DEEP. Underground Storage Tank Regulations Briefing, May 6, 2026. PDF
- Connecticut General Assembly. Chapter 400, including current CGS §20-420. cga.ct.gov
- Connecticut General Assembly. Chapter 541, recording repeal of former CGS §29-320. cga.ct.gov
- U.S. Census Bureau. 2024 ACS 1-year table B25040, House Heating Fuel. data.census.gov
- U.S. Census Bureau. 2024 ACS 1-year table B25035, Median Year Structure Built. data.census.gov
- U.S. Census Bureau. 2024 ACS data-release record. census.gov
- U.S. Energy Information Administration. Winter Fuels Outlook. eia.gov
- InspectAPedia. Heating Oil Storage Tank Size. inspectapedia.com
- OilTankCharts. Why a 275 gallon tank holds about 240. oiltankcharts.com
- Bottini Fuel. How Much Oil Can My Heating Oil Tank Hold?. bottinifuel.com
- C&K Smith Superior. Understanding Home Heating Oil Tank Sizes. cksmithsuperior.com
- Hocon Gas. Heating Oil Basics: How to Read an Oil Tank Gauge. hocongas.com
- Burt's Reliable. How Much Oil Does a 275 Gallon Tank Hold?. burts.com
- HeatingHelp. True oil tank capacity practitioner discussion. forum.heatinghelp.com
The final seven sources are cited only as published secondary definitions and reported amounts in Table 12. They are not used to establish model dimensions, manufacturer chart cells, statutes, regulations or ACS estimates.
Last verified: July 27, 2026 · Dataset version 2026-07-27.2